On grid/off grid transformerless hybrid Inverter.
From 1 to 8 MPPT – with direct MC inputs.
140% solar oversizing input.
10X scalability (parallel operation).
Generator start stop and stand—by auto logic based on
predictive load algorithm.
Multi-redundant DC bus design, single AC and DC failure.
Supports half-wave load and shock load.
HYBO HYBRID SERIE TL | Specs | 120/120 | 180/120 | 180/180 | 240/240 |
MPPT GENERAL PARAMETERS | MPPT BUS Voltage Range ( Min / Max ) | 200-650 V | |||
MPPT Start Voltage | 200 V | ||||
Open Circuit Max Input Voltage | 680 V | ||||
MPPT Low Voltage Cut Off | 130 V | ||||
MPPT | Number of Indepenedent MPPT | 2 | 3 | 3 | 4 |
MPPT Max . Charging Current | 400 A | 600 A | 600 A | 800 A | |
PV Channels Per MPPT | 12 | ||||
Photovoltaic Total Channels | 24 | 36 | 36 | 48 | |
Channel Max , Input Current | 166 A | ||||
MPPT String Max . Input Power Per Channel | 7 kW | ||||
PV Max , Input Power | 168 kW | 252 KW | 252 kW | 336 kW | |
Single MPPT Max . DC Output | 60 kW | ||||
PV Max . Power ( Total output DC ) | 120 kW | 180 kW | 180 kW | 240 kW | |
BATTERY | Min . Battery Voltage | 680 V | |||
Min . Number of Batteires in Series | 15 Battery Modules | ||||
Max . Voltage Battery DC Bus | 934 V | ||||
Max . Number of Batteries in Series | 17 Battery Modules | ||||
Battery Input Channels | 4 | 4 | 4 | 6 | |
Max . Charging / Discharging Power | 120 kW | 180 kW | 180 kW | 240 kW | |
AC SIDE / ON GRID / OFF GRID | Grid Type | 3L + N + PE | |||
Rated Power Output AC Side | 120 kW | 120 kW | 180 kW | 240 kW | |
Rated Current | 172 A | 172 A | 258 A | 344 A | |
Rated Voltage | 400 Vac | ||||
Voltage Range | 400 Vac ± 15 % | ||||
Rated Frequency ( Hz ) | 50 Hz / 60 Hz | ||||
Frequency Range | ± 3 Hz | ||||
Power Factor | -1 ~ +1 | ||||
Frequency Accuracy | 0.2 Hz | ||||
Voltage Ripple | < 3 % | ||||
Current Ripple | < 2 % | ||||
Output Harmonic Wave | < 3 % | ||||
Phase Unbalance Load ( off – grid ) | 100% | ||||
ON / OFF Grid Transfer Time | Min . 20 ms | ||||
ENVIRONMENT | Working Temperature | 20 ° C – 55 ° C ( Over 45 ° C derating ) | |||
Ralatively Humidity | 0 % RH – 95 % RH , non – condensing | ||||
Working Altitude | At 45 ° C , 2000m ( no derating ) , 2000m – 4000m derating | ||||
Noise | < 75 dB | ||||
INTERFACE | Communication | RS485 , CAN . WIFI ( SUNSPEC ) | |||
Protocol | CAN , ModBus TCP , ModBus RTU | ||||
Installation | INDOOR IP 30 / OUTDOOR IP 65 | ||||
Maximum Efficiency | 97.50 % | ||||
Isolation | TransformerLess ( Optional Trafo ) | ||||
Cooling Type | Air cooling , intelligent fan speed regulation | ||||
Dimension ( D x H x W ) ( mm ) | 1150 x 2200 x 850 | 1050 x 2250 x 1350 | |||
Weight | 460 Kg | 520 Kg | 650 Kg | 980 Kg |
See warranty for performance warranty applicability.
See Performance Warranty Terms and the Standard Test Conditions “STC”.
All data is subjected to change without prior notice: Always ask WeCo for the most recent datasheet and manual before purchasing.
No part of this document can be copied or reproducted without WeCo written permission.
HYBO PCS SERIE TL | Specs | PCS 120 | PCS 180 | PCS 240 : | PCS 300 |
BATTERY | Min . Battery Voltage | 680 V | |||
Min . Number of Batteries in Series | 15 Battery Modules | ||||
Max . Battery Voltage | 934 V | ||||
Max . Number of Batteries in Series | 17 Battery Modules | ||||
Battery Input Channels | 4 | 4 | 4 | 6 | |
Max . Charging / Discharging Power | 120 kW | 180 kW | 240 kW | 300 kW | |
AC SIDE / ON GRID / OFF GRID | Grid Type | 3L + N + PE | |||
Rated Power Output AC Side | 120 kW | 180 kW | 240 kW | 300 kW | |
Rated Current | 172 A | 258 A | 344 A | 430 A | |
Rated Voltage | 400 Vac | ||||
Voltage Range | 400 Vac ± 15 % | ||||
Rated Frequency ( Hz ) | 50 Hz / 60 Hz | ||||
Frequency Range | ± 3 Hz | ||||
Power Factor | -1 ~ +1 | ||||
Frequency Accuracy | 0.2 Hz | ||||
Voltage Ripple | < 3 % | ||||
Current Ripple | < 2 % | ||||
Output Harmonic Wave | < 3 % | ||||
Phase Unbalance Load ( off – grid ) | 100% | ||||
ON / OFF Grid Transfer Time | Min . 20 ms | ||||
ENVIRONMENT | Working Temperature | -20 ° C ~ 55 ° C ( Over 45 ° C derating ) | |||
Ralatively Humidity | 0 % RH – 95 % RH , non – condensing | ||||
Working Altitude | At 45 ° C . 2000m ( no derating ) . 2000m – 4000m derating | ||||
Noise | < 75 dB | ||||
INTERFACE | Communication | RS485 , CAN , WIFI ( SUNSPEC ) | |||
Protocol | CAN . ModBus TCP , ModBus RTU | ||||
Installation | INDOOR IP 30 / OUTDOOR IP 65 | ||||
Maximum Efficiency | 97.50 % | ||||
Isolation | TransformerLess ( Optional Trafo ) | ||||
Cooling Type | Air cooling , intelligent fan speed regulation | ||||
Dimension ( D x H x W ) ( mm ) | 1150 x 2200 x 850 | ||||
Weight | 340 Kg | 430 Kg | 590 Kg | 680 Kg |
See warranty for performance warranty applicability.
See Performance Warranty Terms and the Standard Test Conditions “STC”.
All data is subjected to change without prior notice: Always ask WeCo for the most recent datasheet and manual before purchasing.
No part of this document can be copied or reproducted without WeCo written permission.
Technical Data | HYBO 100 TS | HYBO 150 TS | HYBO 250 TS | HYBO 500 TS |
Battery | ||||
Battery Voltage Range ( V ) | 420-850 | 420 – 850 | 420-850 | 500 – 850 |
Max . Charge / Discharge Current ( A ) | 270 | 405 | 673 | 1128 |
AC Output ( On Grid ) | ||||
Max . AC Output Power ( KVA ) | 110 | 165 | 275 | 550 |
Rated Output Power ( kW ) | 100 | 150 | 250 | 500 |
Rated Voltage ( Vac ) | 400 | |||
Voltage Range ( Vac ) | 320 – 460 | |||
Rated Output Current ( A ) | 144 | 216 | 361 | 722 |
Max . Output Current ( A ) | 159 | 238 | 397 | 794 |
Rated Frequency ( Hz ) | 50 / 60 | |||
Frequency Range ( Hz ) | 45-55 / 55-65 | |||
THDI | < 3 % | |||
Power Factor | 1 Lead – 1 Lag ( Configurable ) | |||
AC Format | 3W + N + PE | |||
AC Output ( Off Grid ) | ||||
Rated Voltage ( Vac ) | 400 | |||
THDU | < 1 % Linear , < 1 % Nonlinear | |||
Rated Frequency ( Hz ) | 50 / 60 | |||
Overload Ability | 110 % Long – term | |||
General Data | ||||
Max . Efficiency | 97.1 % | 97.1 % | 97.30 % | 97.50 % |
IP Rating | IP21 | |||
Noise ( dB ) | < 70 | |||
Ambient Temperature | -30 ° C ~ +55 ° C | |||
Cooling Method | Forced Air Cooling | |||
Relative Humidity | 0-95 % non – Condensing | |||
Altitude | 3000m ( Up to 5000m with derating ) | |||
Size ( W x D x H ) ( mm ) | 800 × 800 × 2050 | 800 x 800 × 2050 | 1200 x 800 x 2050 | 1600 × 1050 x 2050 |
Weight ( kg ) | 936 | 1057 | 1582 | 2665 |
Transformation Ratio | 270 / 400 | 270 / 400 | 270 / 400 | 315/400 |
Shutdown Self Consumption ( W ) | < 100 | |||
ON / OFF Grid Transfer Time | Automatic / Seamsless | |||
Display And Communication | ||||
Display | LCD | |||
BMS Communication | RS485 , CAN | |||
EMS Communication | RS485 , TCP / IP | |||
Standards | IEC / EN 62109-1 / -2, IEC / EN 62477-1, IEC / EN 61000-6-2, IEC / EN 61000-4, CGC *NSR 097 / CEI 016 / VDE ( On-Going ) |
See warranty for performance warranty applicability.
See Performance Warranty Terms and the Standard Test Conditions “STC”.
All data is subjected to change without prior notice: Always ask WeCo for the most recent datasheet and manual before purchasing.
No part of this document can be copied or reproducted without WeCo written permission.
HYBO CS Buck mode | HYBRID HYBO BUILT IN TRANSFORMER | |||
PV Buck Mode | ||||
Model | CS100 | CS150 | CS250 | CS500 |
On Grid AC specifications | ||||
Max. Output power (kVA) | 110 | 165 | 275 | 550 |
Rated Output Power (kW) | 100 | 150 | 250 | 500 |
Rated Voltage (V) | 400 | |||
Voltage Range (V) | 320~460 | |||
Rated Current (A) | 144 | 216 | 361 | 722 |
Rated Frequency (Hz) | 50 / 60 | |||
Frequency Range (Hz) | 45~55 – 55~65 | |||
THDi | <3% | |||
Power Factor | 1 lagging – 1 leading (Settable) | |||
AC Connection | 3W+N+PE | |||
Transformer Ratio | 270 / 400 | 270 / 400 | 270 / 400 | 315 / 400 |
Model | CS100 | CS150 | CS250 | CS500 |
Off Grid Specifications | ||||
Max. Output Power (kVA) | 110 | 165 | 275 | 550 |
Rated Power (kW) | 100 | 150 | 250 | 500 |
Rated Voltage (V) | 400 | |||
Rated Current (A) | 144 | 216 | 361 | 722 |
THDU | ≤1% linear; or ≤5% nonlinear | |||
Rated Frequency (Hz) | 50 / 60 | |||
Overload Capacity | 110% Continuous / 150% 10 sec | |||
On to Off-grid Transfer Time | 13ms | |||
Model | CS100 | CS150 | CS250 | CS500 |
High Voltage PV Input ( Buck Mode) | ||||
PV Input Voltage Range (Voc)(V@25°C) | 655-900 | 780-900 | ||
Max. PV Power (kW) MPPT in step of 60kW | 120 / 180 / 240 | 120 / 180 / 240 | 300 / 360 | 600 / 660 / 720 |
MPPT Voltage Range(V@25°C) | 544-747 | 648-747 | ||
buck mode Battery | ||||
Battery Voltage Range (V) | 420-672 | 500-672 | ||
Battery cabinet Composition | Min 8 Max 12 Batteries | Min 9 Max 12 Batteries | ||
Max. Charging Power (kW) | 120 / 180 / 240 | 120 / 180 / 240 | 300 / 360 | 600 / 660 / 720 |
Model | CS100 | CS150 | CS250 | CS500 |
General Data | ||||
Max On and Off grid parallel Units | 10 | |||
Dimension W*D*H (mm) | 1200*800*2050 | 1200*800*2050 | (600*720*2050)*1+1200*800*2050 | (600*720*2,050)*2+1600*1050*2050 |
Weight (kg) | 1120 / 1150 / 1180 | 1250 / 1280/1310 | 1980 / 2010 | 3265/3295/3325 |
Operation Temperature (℃) | -30~55 | |||
Relative Humidity | 0~95% non-condensing | |||
IP Rating | IP20 | |||
Noise Emission (dB) | <70 | |||
Altitude | 4,000m (>3,000 Derating) | |||
Cooling | Forced Air Cooling | |||
Display and Communication | ||||
Display | LCD touch-screen / NooR Smart App | |||
BMS Communication | RS485, CAN | |||
EMS Communication | RS485, TCP/IP | |||
Standards | EN62109-1/-2, EN62447-1, EN61000-6-2, EN61000-6-4, South Africa NRS097-2-1:2017, Pakistan & India IEC62116, IEC61683 |
See warranty for performance warranty applicability.
See Performance Warranty Terms and the Standard Test Conditions “STC”.
All data is subjected to change without prior notice: Always ask WeCo for the most recent datasheet and manual before purchasing.
No part of this document can be copied or reproducted without WeCo written permission.
HYBO CS Boost | HYBRID HYBO BUILT IN TRANSFORMER | |||
PV Boost Mode | ||||
Model | CS100 | CS150 | CS250 | CS500 |
On Grid AC specifications | ||||
Max. Output power (kVA) | 110 | 165 | 275 | 550 |
Rated Output Power (kW) | 100 | 150 | 250 | 500 |
Rated Voltage (V) | 400 | |||
Voltage Range (V) | 320~460 | |||
Rated Current (A) | 144 | 216 | 361 | 722 |
Rated Frequency (Hz) | 50 / 60 | |||
Frequency Range (Hz) | 45~55 -55~65 | |||
THDi | <3% | |||
Power Factor | 1lagging -1leading (Settable) | |||
AC Connection | 3W+N+PE | |||
Transformer Ratio | 270 / 400 | 270 / 400 | 270 / 400 | 315 / 400 |
Model | CS100 | CS150 | CS250 | CS500 |
Off Grid Specifications | ||||
Max. Output Power (kVA) | 110 | 165 | 275 | 550 |
Rated Power (kW) | 100 | 150 | 250 | 500 |
Rated Voltage (V) | 400 | |||
Rated Current (A) | 144 | 216 | 361 | 722 |
THDU | ≤1% linear; or ≤5% nonlinear | |||
Rated Frequency (Hz) | 50 / 60 | |||
Overload Capacity | 110% Continuous / 150% 10 sec | |||
On to Off-grid Transfer Time | 13ms | |||
Model | CS100 | CS150 | CS250 | CS500 |
High Voltage Battery Input ( Boost Mode) | ||||
PV Input Voltage Range (Voc)@25°C | 535-650 | |||
Max. PV Power (kW) | 120 / 180 / 240 | 120 / 180 / 240 | 300 / 360 | 600 / 660 / 720 |
Boost mode Battery | ||||
Battery Voltage Range (V) | 624-850 | 624-850 | ||
Battery Cabinet Composition | Min 11 Max 15 Batteries | |||
boost mode Max. Charging Power (kW) | 120 / 180 / 240 | 120 / 180 / 240 | 300 / 360 | 600 / 660 / 720 |
Model | CS100 | CS150 | CS250 | CS500 |
General Data | ||||
Max On and Off Grid Parallel Units | 10 | |||
Dimension W*D*H (mm) | 1200*800*2050 | 1200*800*2050 | (600*720*2050)*1+1200*800*2050 | (600*720*2,050)*2+1600*1050*2050 |
Weight (kg) | 1120 / 1150 / 1180 | 1250 / 1280/1310 | 1980 / 2010 | 3265/3295/3325 |
Operation Temperature (℃) | -30~55 | |||
Relative Humidity | 0~95% non-condensing | |||
IP Rating | IP20 | |||
Noise Emission (dB) | <70 | |||
Altitude | 4,000m (>3,000 Derating) | |||
Cooling | Forced Air Cooling | |||
Display and Communication | ||||
Display | LCD touch-screen / NooR Smart App | |||
BMS Communication | RS485, CAN | |||
EMS Communication | RS485, TCP/IP | |||
Standards | EN62109-1/-2, EN62447-1, EN61000-6-2, EN61000-6-4, South Africa NRS097-2-1:2017, Pakistan & India IEC62116, IEC61683 |
See warranty for performance warranty applicability.
See Performance Warranty Terms and the Standard Test Conditions “STC”.
All data is subjected to change without prior notice: Always ask WeCo for the most recent datasheet and manual before purchasing.
No part of this document can be copied or reproducted without WeCo written permission.
Sign up to receive the
WeCo Technical Newsletter.
Keep up to date with the latest insights, news, training events, and exclusive content from WeCo, direct to your inbox